Seri-Para I/O unit

ACC-SP16TAGB

This is the interface for connecting signals from the central control device with the SANYO air conditioner unit control network

  • This unit can control and monitor the status up to 16 groups of indoor units (max 64 indoor units)
  • Up to 4 seri-para units can be connected in one system
  • From the central control device, it is possible to set the temperature and to monitor the room temperature or intake air temperature

 Input

  • ON/OFF (Pulse DC24V)
  • Local prohibit (Continuous DC24V)
  • Temp setting (Analog DC1~5V)
  • All ON/OFF (Pulse DC24V)
  • All local prohibit & emergency stop (Continuous DC24V)

 Output

  • On/Alarm/Answer back/Filter sign
  • Room temp (Analog DC4-20mA)
  • All ON/OFF

System example